Nominal power 40 kW
Hot water boiler KTP 40 for combustion of fire wood, short piece wood, fresh saw dust, wet chips and other wet biomass. Another possible alternative fuel is brown and hard coal. The fuels can be mixed. Boilers comply with Class 3 in accordance with the Norm ČSN EN 303 – 5 EKODESIGN.
Special construction of combustion chamber enabling double combustion, i.e. about 80% gasification and about 20% common burning out.
Boilers are a welded structure, inner plates 5 mm thick, outer walls 4 mm thick. All walls of the boiler body are doubled, filled with water, including the grate made of heat resistant pipes.
TECHNICAL DATA
Boiler | |
Nominal output | 40 kW |
Min. output | 24 kW |
Boiler width | 748 mm |
Boiler height | 1285,5 mm |
Boiler depth | 683 mm |
Grate depth | 480 mm |
Chimney height | 1182,5 mm |
Chimney diameter | 219 mm |
Height of water inlet | 252 mm |
Diameter of water inlet and outlet | 2″ |
Max. diam./length of wood | 230/ 460 mm |
Volume of combustion chamber | 98,5 l |
Boiler weight | 415 kg |
Boiler class in accordance with Norm EN 303-5 | 4 |
Efficiency | 75% |
Energy efficiency class | D |
Energy Efficiency Index (EEI) | 74 |
Seasonal energy efficiency | 74 % |
Boiler emissions according to Commission Regulation (EU) No. 2015/1189 | – |
Flow rate of burnt gas – nominal output | 202 m³/h |
Hydraulic boiler loss | 0,4 mbar |
Burning time for nominal output | 2 h |
Size of loading hatch, semicircle – width x height | 395 x 295 mm |
Water volume | 126 l |
Max. operation water overpressure | 2 bar |
Min. operation water overpressure | 0,5 bar |
Testing water overpressure | 4 bar |
Max. operation temperature | 90°C |
Specified chimney draught | 8 až 12 Pa |
Wood consumption for nominal output | 12,8 kg/h |
Temperature of burnt gas for nominal output | 220 – 300°C |
guarantee for the tightness of boiler body 3 years
- guarantee for the tightness of boiler body 3 years
- possibility to burn all kinds of solid fuels
- possibility to burn wet wood, wet biomass and other solid fuels in manual operation
- boilers are designed for low chimney draught 10 – 12 Pa
- boilers include a cooling loop as a protection against overheating
- the boiler output can be adjusted and its service capacity reduced by 40% without any additional devices
- the return water can drop up to 40°C because it goes through the pipe grate near the fire place
This boiler KTP 40 with manual loading can be completed with a high quality Rojek pellet burner and changed to an automatic boiler.